7.2. Check methods
1. Component and check points
(1) Thermistor
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
1) Thermistor characteristic graph
(2) Linear expansion valve
Disconnect the connector, and measure the resistance between terminals with a tester.
Refer to the next page for details.
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Gas pipe thermistor (TH23)
Thermistor R
0
= 15 k±3%
Multiplier of B = 3480 k±2%
0°C 15k
10°C 9.6k
20°C 6.3k
25°C 5.2k
30°C 4.3k
40°C 3.0k
(A) Temperature (°C)
(B) Resistance (k)
Rt = 15 exp { 3480( ) }
1
273+t
1
273
0
10
20
30
40
50
-20 -10 0 10 20 30 40 50
(A)
(B)
Normal Abnormal
1-5 2-6 3-5 4-6 Open or short
White-Red Yellow-Brown Orange-Red Blue-Brown
200 k±10%
(A) Brown (D) Orange
(B) Red (E) Yellow
(C) Blue (F) White
1
2
3
4
5
6
LEV
M
(A)
(B)
(C)
(D)
(E)
(F)
CN60