Mitsubishi Electric MAC 10 Spezifikationen Seite 152

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 228
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 151
8 - 8
Continued from the previous page
8) Set the following contents.
Protocol : TCP
Open system : Unpassive
Fixed buffer communication procedure:
No procedure
Pairing open : Enable
Existence confirmation : No confirm
Host station Port No. : 0401
9) Click the End
button to close the network
parameter Ethernet open settings screen.
10) Click the Router relay parameter
button to
display the Ethernet routing information settings
screen.
The setting of this routine relay parameter is for the
PING test described in Section 8.4.
When performing only the data communication of
this chapter, the setting for this routine relay
parameter is not required.
11) Set the following contents, click the End
button, and then close the Ethernet routing
settings information screen.
Router relay function : Use
Sub-net mask pattern : 255.255.0.0
(This textbook uses
the default of class B.)
Default router IP address : 172.16.1.254
12) Click the End
button to close the "Network
parameters Setting the number of MNET/10H
Ethernet cards" screen.
Continued to the next page
Seitenansicht 151
1 2 ... 147 148 149 150 151 152 153 154 155 156 157 ... 227 228

Kommentare zu diesen Handbüchern

Keine Kommentare